Precision Electronically Compensated Current
Transformer with Remote Load Management

The CMR-I 2x30 is a small-sized electronically compensated current transformer unit for isolated precision current transmission. The through-hole concept and single wire capability enable any user defined current ratio. The unit is dedicated for testing of electricity meters with closed current-potential circuits and for universal step-up/down current transformation applications with excellent accuracy and dynamics.

The CMR-I 2x30 is equipped with Load Monitoring, Protection Circuits and Load Bypass with serial remote control.

The CMR-I 2x30 can be implemented into any existing test system with negligible additional power losses. Current ratio can be set by number of primary and secondary wires passing the hole. The internal electronics of the device assures the specified accuracy for any up/down ratio.

 Highlights
• Standalone through-hole precision electronically compensated transformer with single
  wire capability
• Excellent accuracy and dynamics
• Remote control via serial communication
• Monitoring of individual contact resistance and power loss
• Protection against open circuit and overload
• Programmable load by-pass
• Automatic unused position by-pass
• Easy implementation to existing systems
• Simple user test of functionality and accuracy
• Accuracy maintained for any up or down current transformation
Patent Protection !
 Specifications
CMR-I 2130 CMR-I 2230 CMR-I 2330
  Output / Input Ratio Defined by input and output turns (1:1 for single wire circuit)
  Dynamics > 200 000 (240 A : 1 mA for single wire)
  Max. Ampere-turns 240 A*turn 2 x 240 A*turn 3 x 240 A*turn
  Max. Output Power 72 VA @ 240A 2 x 72 VA @ 240A 3 x 72 VA @ 240A
  Max. Output Voltage 0.3 V * Ns
  Operating Frequency 45 .. 65 Hz
  Max. Load Resistance 0.05 W * Ns²
  Primary Current Range 1 mA / NP .. 240 A / NP
  Max. Amplitude/Phase
  Error
0.05 % / 0.03° (CMR-I 2x30A)
0.02 % / 0.01° (CMR-I 2x30E)
0.01 % / 0.005° (CMR-I 2x30S)
  Comunication RS-422
  Protection Overload, Open Circuit
  Hole Diameter 26 mm
  Size (L x H x D) 160 x 90 x 120 mm 160 x 170 x 120 mm 160 x 250 x 120 mm
  Weight approx. 5 kg approx. 7 kg approx. 9 kg
Ns … number of secondary turns,    Np … number of primary turns
   PSCI 1220A
Power Supply for up to 60 single phase, up to 30
two phase or up to 20 three phase CMR-I units
  Input Voltage Range 85 .. 264 VAC / 50 .. 60 Hz
  Size (L x H x D) 100 x 118 x 220 mm
  Weight approx. 2 kg
 Download

Product Leaflet (screen optimized)
  cmri_ll200610 [131 kB]

Product Leaflet (print optimized)
  cmri_ll200610 [1078 kB]

Article : Testing of electricity meters with interconnected current and voltage circuits
  a_clink.pdf [23 kB]


Precision Electronically Compensated Current Transformer
CMR-I 2330

CMR-I Power Supply PSCI 1220A

CMR-I usage